Modular Fuse Blocks for Class J fuses-CH Series
Fuse Holders and Blocks - Class J
modular fuse holders
CH _ _ J _
Specifications
Decription:
IP-20 finger-safe, 1- to 3- pole Class J fuse holder with DIN rail or panel mounting.
Construction:
Molded polyester housing, nickel-plated brass contacts and stainless steel DIN rail retaining spring.
Ratings:
Agency Information:
CE, UL 512/CSA 22.2.
Features and Benefits:
@ New, easyIDo indication window provides power-off Indication with choice of local indication (indication can be retrofitted).
@ Versatile 1-, 2- and 3-pole versions in 30A or 60A ratings with dual wire rated connections simplify wiring.
@ Improved electrical safety with IP20 finger-safe construction with lock-out/tag-out feature. 3-phase fuse extraction assures all phases are opened for service work.
@ Flexible panel/35mm DIN rail mounting mounting options
@ Versatile 1-, 2- and 3-pole versions in 30A or 60A ratings with dual wire rated connections simplify wiring.
@ Improved electrical safety with IP20 finger-safe construction with lock-out/tag-out feature. 3-phase fuse extraction assures all phases are opened for service work.
@ Flexible panel/35mm DIN rail mounting mounting options
Flammability Rating:
UL 94V0 (white).
Accessories:
@ Field installable local indication
Operating Temperature:
+105/-30/C (+221/-22/F).
Poles:
1-, 2- or 3-Pole.
Wire Range:
1-18 AWG CU solid and stranded conductors with single and dual wire ratings. See Catalog Numbers table for details.
Catalog Numbers:
See Catalog Numbers table below.
Dimensions (mm) :
30A: | 1-Pole 32 W X 70 D X 115 H |
2-Pole 64 W X 70 D X 115 H | |
3-Pole 96 W X 70 D X 115 H | |
60A: | 1-Pole 40 W X 83 D X 125 H |
2-Pole 80 W X 83 D X 125 H | |
3-Pole 120 W X 83 D X 125 H | |
Torque Rating:
10-18 AWG 24 in-lb.
1-8 AWG 35 in-lb.
1-8 AWG 35 in-lb.
Catalog Number | Amp Rating | Volts | # of Poles | IP-20 Finger-Safe | Mounting | Padlockable | Local Indication | AWG Wire Range | Note |
CH30J1 | 30 | 600 | 1 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH30J1I | 30 | 600 | 1 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH30J2 | 30 | 600 | 2 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH30J2I | 30 | 600 | 2 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH30J3 | 30 | 600 | 3 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH30J3I | 30 | 600 | 3 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J1 | 60 | 600 | 1 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J1I | 60 | 600 | 1 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J2 | 60 | 600 | 2 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J2I | 60 | 600 | 2 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J3 | 60 | 600 | 3 | Yes | 35mm DIN/ Panel | Yes | easyID* | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |
CH60J3I | 60 | 600 | 3 | Yes | 35mm DIN/ Panel | Yes | Neon** | 1-18 | * easyID™ viewing window, requires use of Cooper Bussmann LPJ_SPI permanent indication fuses. ** Indication non-fuse dependent. |