High Speed Fuses - Square Body US Style,690V/700V (IEC),40-2000A (-FU/115 Without Indicator)

High Speed Fuses - Square Body US Style
690V/700V (IEC)

 

40-2000A (-FU/115 Without Indicator)
Specifications
Decription:
Square body US style high speed fuses.
Dimensions:
See dimensions illustration.
Ratings:
Volts:- 690Vac (IEC)
 - 700Vac (UL)
Amps:- 40-200A
IR:- 200kA RMS Sym.
Agency Information:
CE, Designed and tested to/IEC 60269: Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition/ CSA Component Acceptance status.
Features and Benefits:
@ Excellent dc performance
@ Low arc voltage and low energy let-through (I2t)
@ Low watts loss
@ Superior cycling capability
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Note:
URated voltage (IEC) 600V.
aRated voltage (IEC) 550V.
@ Watts loss provided at rated current.
@ Microswitch indicator ordered separately.
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Data Sheet:
17056314 (Size 1*) 17056316 (Size 1) 17056318 (Size 2) 17056320 (Size 3) , ,
Catalog Number Size Rated Current RMS-Amps Pre-arc I2t (A2 Sec) Clearing at 660V - I2t (A2 Sec) Watts Loss Dimensions (mm) Size A Dimensions (mm) Size B Dimensions (mm) Size B** Dimensions (mm) Size C1 Dimensions (mm) Size C1** Dimensions (mm) Size C2 Dimensions (mm) Size C2** Dimensions (mm) Size D Dimensions (mm) Size E Dimensions (mm) Size H Dimensions (mm) Size I Note
170M4217                                  
170M3708 1* 40 40 270 9 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3709 1* 50 77 515 11 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3710 1* 63 115 770 14 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3711 1* 80 185 1250 18 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3712 1* 100 360 2450 21 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3713 1* 125 550 3700 26 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3714 1* 160 1100 7500 30 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3715 1* 200 2200 15000 35 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3716 1* 250 4200 28500 40 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3717 1* 315 7000 46500 50 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3718 1* 350 10000 68500 55 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3719 1* 400 15000 105000 60 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3720 1* 450 21000 140000 65 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3721 1* 500 27000 180000 70 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3722 1* 550 34000 230000 75 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M3723 1* 630 48500 325000 80 50 110 148 85 123 72 110 59 45 20 10 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4708 1 200 1650 11500 45 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4709 1 250 3100 21000 55 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4710 1 315 6200 42000 58 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4711 1 350 8500 59000 60 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4712 1 400 13500 91500 65 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4713 1 450 17000 120000 70 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4714 1 500 25000 170000 72 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4715 1 550 34000 23000075 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4716 1 630 52000 350000 80 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4717 1 700 69500 465000 85 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4718 1 800 105000 725000 95 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4719 1 ‡900 155000 ‡850000 100 50 136 157 104 126 78 100 69 53 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5708 2 400 11000 74000 65 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5709 2 450 15500 105000 70 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5710 2 500 21500 145000 75 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5711 2 550 28000 190000 80 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5712 2 630 41000 275000 90 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5713 2 700 60500 405000 95 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5714 2 800 86000 575000 105 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5715 2 900 125000 840000 110 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5716 2 1000 180000 1250000 115 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5717 2 1100 245000 1600000 120 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M5718 2 1250 365000 2400000 130 50 135 159 105 125 78 99 77 61 25 14 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6708 3 500 14000 95000 95 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6709 3 550 19500 135000 100 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6710 3 630 31000 210000 105 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6711 3 700 44500 300000 110 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6712 3 800 69500 465000 115 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6713 3 900 100000 670000 120 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6714 3 1000 140000 945000 125 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6715 3 1100 190000 1300000 130 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6716 3 1250 290000 1950000 140 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6717 3 1400 370000 2450000 155 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6718 3 1500 460000 3100000 160 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6719 3 1600 580000 3900000 160 51 135 155 106 12577 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6720 3 †1800 880000 †5250000 165 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M6721 3 ‡2000 1150000 ‡6350000 175 51 135 155 106 125 77 97 92 76 36 16 **Valid for fuses type -FU/115
& -FKE/115.
1mm = 0.0394" /
1" = 25.4mm
170M4617