High Speed Fuses - Square body flush end contact,690V/700V (IEC/UL),40-2000A (-BKN/- Type K Indicator For Micro)

High Speed Fuses - Square body flush end contact
690V/700V (IEC/UL)


40-2000A (-BKN/- Type K Indicator For Micro)
Specifications
Decription:
Square body flush end contact high speed fuses.
Dimensions:
See dimensions illustrations.
Ratings:
Volts:- 690Vac (IEC)
 - 700Vac (UL)
Amps:- 40-2000A
IR:- 200kA RMS Sym.
Agency Information:
CE, Designed and tested to/IEC 60269: Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition / CSA Component Acceptance Status.
Features and Benefits:
@ Excellent dc performance
@ Low arc voltage and low energy let-through (I2t)
@ Low watts loss
@ Superior cycling capability
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Note:
URated voltage (IEC) 600V. aRated voltage (IEC) 550V. @ Watts loss provided at rated current. @ Microswitch indicator ordered separately.
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Data Sheet:
17056314 (Size 1*) 17056316 (Size 1) 17056318 (Size 2) 17056320 (Size 3)
Catalog Number Size Rated Current RMS-Amps Pre-arc I2t (A2 Sec) Clearing at 660V I2t (A2 Sec) Watts Loss Dimensions (mm) Size A Dimensions (mm) Size B Dimensions (mm) Size D Dimensions (mm) Size E Dimensions (mm) Size F Dimensions (mm) Size F** (in) Dimensions (mm) Size G Dimensions (mm) Size H Note
170M3458 1* 40 40 270 9 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3459 1* 50 77 515 11 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3460 1* 63 115 770 14 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3461 1* 80 185 1250 18 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3462 1* 100 360 2450 21 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3463 1* 125 550 3700 26 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3464 1* 160 1100 7500 30 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3465 1* 200 2200 15000 35 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3466 1* 250 4200 28500 40 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3467 1* 315 7000 46500 50 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3468 1* 350 10000 68500 55 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3469 1* 400 15000 105000 60 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3470 1* 450 21000 140000 65 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3471 1* 500 27000 180000 70 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3472 1* 550 34000 230000 75 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M3473 1* 630 48500 325000 80 50 51 59 45 M8 5/16" - 18 UNC-2B 5 ø17 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4458 1 200 1650 11500 45 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4459 1 250 3100 21000 55 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4460 1 315 6200 42000 58 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4461 1 350 8500 59000 60 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4462 1 400 13500 91500 65 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4463 1 450 17000 120000 70 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4464 1 500 25000 170000 72 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4465 1 550 34000 230000 75 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4466 1 630 52000 350000 80 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4467 1 700 69500 465000 85 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4468 1 800 105000 725000 95 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M4469 1 ‡900 155000 ‡850000 100 50 51 69 53 M8 5/16" - 18 UNC-2B 8 ø20 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1m, m = 0.0394"/1"=25.4mm
170M5458 2 400 11000 74000 65 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5459 2 450 15500 105000 70 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5460 2 500 21500 145000 75 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5461 2 550 28000 190000 80 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5462 2 630 41000 275000 90 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5463 2 700 60500 405000 95 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5464 2 800 86000 575000 105 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5465 2 900 125000 840000 110 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5466 2 1000 180000 1250000 115 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5467 2 1100 245000 1600000 120 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M5468 2 1250 365000 2400000 130 50 51 77 61 M10 3/8" - 16 UNC-2B 10 ø24 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6458 3 500 14000 95000 95 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6459 3 550 19500 135000 100 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6460 3 630 31000 210000 105 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6461 3 700 44500 300000 110 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6462 3 800 69500 465000 115 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6463 3 900 100000 670000 120 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6464 3 1000 140000 945000 125 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6465 3 1100 190000 1300000 130 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6466 3 1250 290000 1950000 140 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6467 3 1400 370000 2450000 155 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6468 3 1500 460000 3100000 160 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6469 3 1600 580000 3900000 160 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6470 3 †1800 880000 †5250000 165 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm
170M6471 3 ‡2000 1150000 ‡6350000 175 51 53 92 76 M12 1/2" - 13 UNC-2B 10 ø30 **Valid for fuses type -G/- & -GKN/-.
NB: B=65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394"/1"=25.4mm