FEE - BS 88 style stud-mount fuses.

High Speed Fuses - British BS 88
690V: 6-710A

 

FEE
Specifications
Decription:
BS 88 style stud-mount fuses.
Dimensions:
See Dimensions illustrations.
Ratings:
Volts:- 690Vac/350Vdc
Amps:- 6-710A
IR:- 200kA RMS Sym.
Agency Information:
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. MT and MMT o 350Vdc (IEC) rating. Consult Cooper Bussmann for UL Recognition status.
Features and Benefits:
@ Excellent cycling capability
@ Excellent dc performance
@ Low arc voltage and low energy let-through (I2t)
@ Low watts loss
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Note:
@ Watts loss provided at rated current.
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Data Sheet:
Catalog Number Type Rated Current RMS-Amps Pre-arc I2t (A2 Sec) Clear at 415V - I2t (A2 Sec) Clear at 660V - I2t (A2 Sec) Watts Loss
100FEE FEE 100 400 1600 2400 24
120FEE FEE 120 540 1900 3100 32
140FEE FEE 140 850 3800 3800 36
160FEE FEE 160 1000 3700 5700 46
180FEE FEE 180 1400 5300 8400 46
200FEE FEE 200 1900 7100 11400 52