LCT - BS 88 style stud-mount fuses.

High Speed Fuses - British BS 88
240V: 6-900A


LCT
Specifications
Decription:
BS 88 style stud-mount fuses.
Dimensions:
See Dimensions illustrations.
Ratings:
Volts:- 240Vac/150Vdc
Amps:- 6-900A
IR:- 200kA RMS Sym.
Agency Information:
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. All fuses above have been tested at 318Vac. Consult Cooper Bussmann for specific UL Recognition status.
Features and Benefits:
@ Excellent cycling capability
@ Excellent dc performance
@ Low arc voltage and low energy let-through (I2t
Typical Applications:
@ DC common bus
@ DC drives
@ Power converters/rectifiers
@ Reduced voltage starters
Arc Voltage:
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Total Clearing I2t:
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Note:
@ Watts loss provided at rated current.
Power Losses:
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Data Sheet:
Catalog Number Rated Current RMS-Amps Pre-arc I2t (A2 Sec) Clear at 120V - I2t (A2 Sec) Clear at 240V - I2t (A2 Sec) Watts Loss Type
6LCT 6 2 6 9 1.0 LCT
10LCT 10 3.8 12 22 2.5 LCT
12LCT 12 7 22 32 2.5 LCT
16LCT 16 20 50 100 2.5 LCT
20LCT 20 25 80 160 4.0 LCT