E-rated fuses,CL-14,ECL155

Medium Voltage Fuses and Fuse Links 
E-rated fuses,
CL-14


ECL155
Specifications
Decription:
E-rated medium voltage, current-limiting fuses for transformer and feeder protection.
Construction:
Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration.
Ratings:
Volts:- 15.5kV
Amps:- 10-300A
IR:- 63kA Sym. (10-200A)
 - 50kA Sym. (250-300A)
Agency Information:
Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40.
Features and Benefits:
@ Clip-lock double barrel fuse design assures positive installation
@ The filament wound, glass epoxy fuse tube provides UV and moisture protection, making these medium voltage fuses suitable for both indoor and outdoor applications
@ Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes
@ 50/60 Hz operating frequency make these fuses applicable world-wide
Typical Applications:
@ 15.0 kV Transformer Primary Protection
@ 15.0 kV Feeder Circuit Protection
@ 15.0 kV Voltage Switches
@ 15.0 kV Metal-enclosed Switchgear
Note:
Current-limiting medium voltage fuses are classified into three categories:
1. Full Range - defined by ANSI as ia fuse capable of interrupting all currents from the maximum rated interrupting current down to the minimum continuous current that causes melting of the fusible element(s), when the fuse is applied at the maximum ambient temperature specified by the manufacturer.@ It is able to interrupt any normal 60 cycle current that will melt its element.
2. General Purpose - defined by ANSI C37.40 as ia fuse capable of interrupting all currents from the maximum rated interrupting current down to the current that causes melting of the fusible element in one hour.@ Not all currents fall within this range. It is possible to receive an overcurrent lower than the value given by the one hour criterion.
Catalog Number Construction (Example):
Catalog Number Voltage Rating Ampere Rating
ECL 155 300E
155 = 15.5 kV
Data Sheet:
Catalog Number Amp Rating Voltage IR Voltage Max Sym. # of Barrels Style Ferraz-Shawmut New Catalog # Ferraz-Shawmut Old Catalog #
ECL155-10E 10 15.5kV 63kA 1 Clip-Lock A155C1DORO-10E 225-007-967
ECL155-15E 15 15.5kV 63kA 1 Clip-Lock A155C1DORO-15E 225-007-968
ECL155-20E 20 15.5kV 63kA 1 Clip-Lock A155C1DORO-20E 225-007-969
ECL155-25E 25 15.5kV 63kA 1 Clip-Lock A155C1DORO-25E 225-007-970
ECL155-30E 30 15.5kV 63kA 1 Clip-Lock A155C1DORO-30E 225-007-971
ECL155-40E 40 15.5kV 63kA 1 Clip-Lock A155C1DORO-40E 225-007-972
ECL155-50E 50 15.5kV 63kA 1 Clip-Lock A155C1DORO-50E 225-007-973
ECL155-65E 65 15.5kV 63kA 1 Clip-Lock A155C1DORO-65E 225-007-974
ECL155-80E 80 15.5kV 63kA 1 Clip-Lock A155C1DORO-80E 225-007-975
ECL155-100E 100 15.5kV 63kA 1 Clip-Lock A155C1DORO-100E 225-007-976
ECL155-125E 125 15.5kV 63kA 1 Clip-Lock A155C2DORO-125E 225-007-977
ECL155-150E 150 15.5kV 63kA 2 Clip-Lock A155C3DORO-150E 225-007-978
ECL155-200E 200 15.5kV 63kA 2 Clip-Lock A155C3DORO-200E 225-007-979
ECL155-250E 250 15.5kV 50kA 2 Clip-Lock A155C3DORO-250E 225-007-980
ECL155-300E 300 15.5kV 50kA 2 Clip-Lock A155C3DORO-300E 225-007-981