British Standard VT Fuses,Potential transformer fuses,CAV

Medium Voltage Fuses and Fuse Links 
British Standard VT Fuses,
Potential transformer fuses


CAV
Specifications
Decription:
British Standard VT fuses with low current
ratings for use in voltage transformers or operating
transformers to provide isolation of the associated system in the event of faults in the transformer circuit.
Dimensions:
See Basic Catalog Numbers table.
Ratings:
E-Rated:- See single asterisk in Basic Catalog
 Numbers table
Volts:- 3.6-38kV (See Basic Catalog Numbers
 table)
Amps:- 2-15A (See Basic Catalog Numbers
 table)
IR:- 25-80kA (See Basic Catalog Numbers
 table)
Agency Information:
BS2692-1 and IEC60282-1
Features and Benefits:
@ Physically dimensioned for retrofitting in existing hardware.
@ Space saving size.
Typical Applications:
@ Medium Voltage Potential Transformers
@ Small Medium Voltage Service Transformers
Build-A-Code:
Catalog Number Build-A-Code
kV Basic Catalog Number Amps
_ _ _ _ _ _ _ _ _ _ _
Note:
Type CAVH are fitted with a striker pin for indication.
* E-Rated fuses
**For clean indoor applications only.
Catalog Number Volts Amp Ratings Length Diameter IR
CAV 3.6kV 2 8.66 (220) 1.63 (41.4) 40KA
CAV* 5.5kV 15 7.375 (187.3) 1.63 (41.4) 40KA
CAVH* 5.5kV 0.5, 1, 2 7.375 (187.3) 1.63 (41.4) 50KA
CAV 7.2kV 2, 10 8.66 (220) 1.63 (41.4) 40KA
CAV 12kV 2 8.66 (220) 1.63 (41.4) 40KA
CAV* 15.5kV 0.5, 1, 2, 3, 7 12.87 (326.9) 1.63 (41.4) 80KA
CAVH* 15.5kV 0.5, 1, 2 12.87 (326.9) 1.63 (41.4) 80KA
CAVH* 38kV 0.5, 1, 2 17.32 (439.9) 1.63 (41.4)  
CAV 17.5kV 2, 4, 6, 10 8.66 (220) 1.63 (41.4) 40KA
CAV 24kV 2, 3, 4 13.39 (340.1) 1.63 (41.4) 40KA
CAV 36kV 2, 4 17.32 (439.9) 1.63 (41.4) 40KA
CAVH 36kV 2 17.32 (439.9) 1.63 (41.4) 40KA
CAV* 38kV 4 17.32 (439.9) 1.63 (41.4) 40KA